Tony1965
In February 2020 I installed a JC Refrigeration Hvac 1200 & 1210 unit (AC Compressor 110 V - 120 V, 0.8 A, 96.4 W, 56% duty cycle @ 80 ° F Amb.) in my RV.

After installation, the unit has been running smoothly until today, when I noticed that the refrigerator temperature was optimal, while the freezer temperature was too high.

I thought that the unit had activated the defrost procedure but it is not, the temperatures are definitely abnormal.

Today, with a wireless thermometer, I register 4 ° C in the refrigerator and a good 19 ° C in the freezer. I don't see any error messages on the display, there is no more ice in the freezer or in the icemaker; there is no ice in the refrigerator fins either, as the fans are always running.

Do you have any ideas on a possible solution?
Reply 0 0
Jr Lambright
the first thing we would recommend is to wire the compressor direct, see attached, what this does is bypass all the original controls and will show us which is at fault the unit or the controls 
Reply 0 0
Tony1965
OK, I'll do this test and let you know.

Thanks for now.
Reply 0 0
Tony1965
OK, I have wired diretctly the compressor.
 
Should the refrigerator be switched on or off during the test?

Not knowing it, I turned on the refrigerator, also to ensure the functioning of the fans.

After a couple of hours the temperature dropped significantly, both in the freezer and in the fridge.

I checked the compressor temperature and it reached almost 60 °C; all fans are spinning.

Obviously, the error message "AC no" appears on the refrigerator display.

So the problem doesn't seem to lie in the compressor.
Reply 0 0
Jr Lambright
Yes that sounds like the control board is going to be the factor here, what we would recommend in this scenario is to replace and bypass the Norcold boards completely by using our Universal controller https://jc-refrigeration.com/product/dutchaire-universal-fridge-control-120v/
Reply 0 0
Tony1965
Couldn't it be a thermistor fault?
Reply 0 0
Tony1965
I forgot that I have the Dinosaur Thermistor Simulator for Norcold Refrigerators, I could do a check with this tester.
Could it be useful, what do you think?
Reply 0 0
Jr Lambright
Not sure, not really familiar with that style, but yes thermistors are the ones responsible to turn the fridge on and off and if its turning off to quick then yes that could be the culprit, that would be a good start point. 
Reply 0 0
Craigch
I'm having this issue too! Tony1965 were you able to figure out if the thermistor was the culprit? Our fridge temp is 34 degrees and the freezer is 63 degrees.
Reply 0 0
Tony1965
I am going to check the thermistor.
I also have the Dinosaur tester (https://www.dinosaurelectronics.com/Thermistor_simulator_Nor.html), the problem is that the attached instructions are not clear at all.
As soon as will be able to check it, I will write it down.
However, the compressor, if connected directly to the 120 V socket, works and cools the refrigerator well.
In an emergency situation, I think you can keep it like that for a while, maybe taking it off at night for a few hours, to let it rest.
I created a cable on purpose, as indicated by Jc Refrigeration, only I added a switch, to avoid touching the sockets often in a tight and uncomfortable environment; so I can attach and detach the compressor with just one click.
Reply 0 0
Tony1965
I'm having a little doubt!
On page 64 of the HVac unit installation manual it says:

"Go to the inside of your RV and turn your refrigerator control“ ON ”. (RA) Then push the mode button (YA) and set it onto LP mode. After a few seconds your compressor should start up and run. You can now set the temp (BA), we recommend setting it to 4 and then after approx. 6 hours, then adjust up or down to reach the desired temp inside the fridge".
LP mode???? Is this an error?
Or was I wrong, after two years, setting the control panel to" AC "instead of" LP "?
Reply 0 0
balvert
My Norcold dual compressor HVAC runs in “LP” mode per the instructions. 
Reply 0 0
Jr Lambright
 In answer to the Lp Mode versus AC mode, approx. 2 yrs. ago we came out with a controller that works off the LP side and gets rid of the NOAC code that used to pop up, so if you are used to run it on AC mode then you will continue to run it that way, it's all dependent on your controller you have
Reply 0 0
Tony1965
Well, good to know.
Reply 0 0
Tony1965
Today I repaired the on-board refrigerator by replacing the original Norcold thermistor with an Articca Adjustable Replacement Thermistor.

To simplify the thermistor replacement operations, instead of disconnecting the thermistor cable on the board, I cut off the power supply to the electronic board, both the 120 V and the 12 V.

After having replaced and placed the new thermistor, I restored power to the board, first at 12 V, then at 120 V, restoring voltage from the main switch and then turning on the refrigerator from its switch.

The temperature was set to the minimum possible by the refrigerator controls, while an average value was set in the Articca thermistor, reactivating the internal fans of the refrigerator.

At present, the temperature of the freezer compartment is -11 °C, while that of the refrigerator is 2 °C.

The test will end within 24 hours.
Reply 0 0