Shep Kuester Shep

This problem cropped up before, but resolved on its own. The compressor comes on, then shuts down seconds later. After about 1 minute, it cycles again like that. I can hear some “clicking” sounds from the digital board or the small board next to it. The red light on the small board does not come on or blink. 

I unplugged from DC and let rest about 5 minutes, then reattached. No difference.  Double checked all wire connections. Any suggestions? And of course, this happens on the weekend!

Reply 0 0
Jr Lambright
this would have to be a low voltage issue to where the 12V will drop below 10.4V in a split second when the compressor comes on, our 12V compressors have a built in low battery saver , so when the compressor starts have a 12V meter hooked to your 12V power wires behind the fridge and see what they drop to. or another way to test is to put 12V directly to the compressor and see if it runs then, if the low voltage is not the issue then we should look at adding the power relay kit https://jc-refrigeration.com/product/power-relay-kit-u/     to get the 12V away from the board where 120V used to go in and this will then turn your compressor on thru a external relay, and will put 120V to the board which will make the board think it is using 120V to power the fridge. this is rare this needs to be added but its a option if its not your low voltage
Reply 0 0
Shep Kuester Shep
After I posted, this is what happened. I plugged and unplugged the power, with no results. I let it sit for a while, and then it came on. It cooled down the unit. However, when the relay tried to turn it on again, it repeated the original problem. Last night I unplugged and plugged it in multiple times, this time working. This morning it was off, same problem.

Saw your reply. I tested with the volt meter. V dropped below 10V for just a fraction of a second, and the unit shut down, just as you said it might do. I'm using the same 12V coach line that was originally connected to the fridge. While testing, I accidentally touched the + wire to a piece of metal, blowing the fuse. Put a new fuse in the line, reconnected the line to the fridge, and it immediately worked properly. I am waiting to see if it cycles properly. I can't imagine a fuse as being the culprit. I'll check this afternoon to see if the problem returns. If so, I will order the suggested kit. This happened a couple months ago, then went away until yesterday. I have no idea what would cause this sudden dip in V. Any ideas?

For anyone reading this thread who is considering switching to a DC or AC compressor, I LOVE my DC compressor! It draws only 1.25KW/day. My old system used 12KW on electric, and would empty a 30# propane bottle in 6 days. And temps varied widely with outdoor temps. for full-timers who boondock a lot, this is a major concern. Even when we were in 100 degree temps in Nevada, my DC compressor chugged right along, keeping the fridge in the middle 30's. Once this problem is fixed, we will be back at full working function again. I will NEVER go back to an ammonia powered fridge!
Reply 0 0
Jr Lambright
OK on your 2118 Norcold the wires behind the fridge are very seldom big enough to handle the load of the kick on the compressor, the relay power kit will not fix this issue, its the low voltage that's causing the drop out. its doing what its supposed to do,i would recommend biting the bullet and running a new 10ga wire from the fridge to the battery and life will be good again
Reply 0 0
Shep Kuester Shep
You do know I don't love you any more? 😁 Thankfully, we are parked in the driveway of a relative for a couple weeks, so off to get 10ga wire. It's a level gravel driveway, so won't be too painful to run the wire. I'll post again after the job is done. I HATE electrical! Just voicing my opinion. I will put a 15A fuse in the line, easily accessible for the future. Thanks for the quick answer.
Reply 0 0
Jr Lambright
unfortunalty this is one we almost always end up running a new wire, there are a lot that are good but for some reason on the 2118 the wires they run for them are just a tad small or they go to far with them
Reply 1 0
Shep Kuester Shep
I ran the 10ga wire today. Instead of dropping the belly, I decided to go external, using a 1/2” flexible conduit to protect the wires. Power is from a 12V node in the front battery compartment. With the help of a little Vaseline, the wires slipped through the conduit easily. I added a 15A fuse in the fridge compartment where I can easily get at it if there is ever a need. Tomorrow I’ll change the thermistor for the Articca thermostat. 
Reply 0 0
Shep Kuester Shep
DC compressor has been working great after changing out for the 10ga wire. A couple days ago the compressor just stopped. I cut power, reconnected, and it worked fine. Two days later, same thing. it worked steady for 3 days. Last night the fridge was 35 and freezer 4. This morning, compressor was off again. Turning system off and on fixed it.

I'm thinking I have a defective power board. Any suggestions?
Reply 0 0
Jr Lambright
boy you got me spinning on this one, not quite sure, look on your manual, do they have a reset for the board, this fridge is relatively new so we don't have a lot of experience with this one.........  

or try to unclip the thermister from the light and see if it still does it, i will do some research and be back to you
Reply 0 0
Shep Kuester Shep
I will some research also. There is one thing that may be impacting this. During install, one of the wires cut is the red wire to the small control board in the photo. With that wire cut, this board is essentially useless, since the green wire is a ground wire. During my search, people do a reset by using a strong magnet to the side of this small board, especially when the red light is lit. Not being connected, it is not lit, and I couldn't do a reset anyway. I am using the Articca thermostat. The weird factor is that the compressor goes on and off normally for days, then suddenly shuts off. This is why my first suspicion is a faulty control board. This board has gone through a lot with the previous ammonia system, so I don't think the compressor is causing this; it is simply "following orders" from the control board. Just my opinion.
IMG_6980.jpg 
Reply 0 0
Jr Lambright
i would tend to think this would be a thermister issue, the thermisters resistance to the board is what trips the relay to start the compressor, and if the board does not throw a code yet the compressor does not start it would sound like the thermister is just sitting there letting on its cold enough and not sending the signal to the board to close the relay to start the compressor. i would keep my eyes on it and once it happens again unclip the thermister from the light and then snap back on again and see if that starts it, if it does then the board is not the issue if it still does not go then i would lean towards the board. the pic you have is the safety control for the gas/elect unit and this is completely out of the circuit and no longer needed so this will have no bearing on the board any more at all
Reply 0 0
Shep Kuester Shep
I disconnected the Articca thermostat and rewired it, making sure there is a really good connection. I will report back on results. If nothing stops in 4 days, I'll consider it fixed, blaming the problem on a poor connection with the thermostat. On this model, the thermistor/thermostat is wired to the fan.
Reply 0 0
Shep Kuester Shep
Everything worked fine for 2 days, then same problem. I forgot and shut power and reconnected. I even took the thermostat wires apart and reconnected to make sure there is a firm connection. Worked perfectly for almost four days, freezer at 4, and fridge at a steady 35. This morning temps are up and fan not working. Disconnected thermostat wire and reconnected. Fan came on and unit is cooling down. for my unit, the thermostat is powered through the fan, not the light. The only item I have not replaced is the control board.
Reply 0 0
Jr Lambright
we had one similar to this first of the week, we ended up changing both the thermister and board and the problem cleared, shall i arrange to send you a new control board?
Reply 0 0
Shep Kuester Shep
Yes, please. You sure have been patient and helpful during this process. I really appreciate it. I'm desperate to have a "safe" supply of ice cream again! 😁